# Modbus Saia Burgess Controls Binding
|
||||
|
||||
This binding interfaces the energy meter series ALD1 by Saia Burgess Controls (SBC) via Modbus.
|
||||
|
||||
## Supported Things
|
||||
|
||||
The following Things are supported:
|
||||
|
||||
- `ald1Unidirectional`: 1-phase 32A one-way energy meter ALD1D5FD00A3A00
|
||||
- `ald1Bidirectional`: 1-phase 32A two-way energy meter ALD1B5FD00A3A00
|
||||
|
||||
## Discovery
|
||||
|
||||
This binding does not support discovery.
|
||||
|
||||
## Thing Configuration
|
||||
|
||||
The following configuration parameter applys to `ald1Unidirectional` and `ald1Bidirectional`.
|
||||
|
||||
| Name | Description | Type | Required |
|
||||
|---------------|------------------------------------------|---------|----------|
|
||||
| pollInterval | Time between polling the data in ms | Integer | yes |
|
||||
|
||||
The Thing needs a Modbus serial slave Bridge to operate.
|
||||
|
||||
One of the following serial settings need to be configured in the Bridge:
|
||||
|
||||
- 9600 baud, 2 stop bit, no parity
|
||||
- 9600 baud, 1 stop bit, even parity
|
||||
- 9600 baud, 1 stop bit, odd parity
|
||||
|
||||
## Channels
|
||||
|
||||
The following Channels apply to `ald1Unidirectional` and `ald1Bidirectional` if not stated otherwise.
|
||||
|
||||
| Name | Type | Description |
|
||||
|---------------------|--------------------------|---------------------------------------------------------------|
|
||||
| total_energy | Number:Energy | Energy Total |
|
||||
| partial_energy | Number:Energy | Energy Counter Resettable (only unidirectional meter) |
|
||||
| feeding_back_energy | Number:Energy | Energy Feeding Back (only bidirectional meter) |
|
||||
| voltage | Number:ElectricPotential | Effective Voltage |
|
||||
| current | Number:ElectricCurrent | Effective Current |
|
||||
| active_power | Number:Power | Effective Active Power (negative numbers mean feeding back) |
|
||||
| reactive_power | Number:Power | Effective Reactive Power (negative numbers mean feeding back) |
|
||||
| power_factor | Number:Dimensionless | Power Factor |
|
||||
|
||||
## Full Example
|
||||
|
||||
### .items
|
||||
|
||||
```
|
||||
Number:Energy ALD1_Total_Energy "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:total_energy"}
|
||||
Number:Energy ALD1_Feeding_Back_Energy "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:feeding_back_energy"}
|
||||
Number:ElectricPotential ALD1_Voltage "[%d %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:voltage"}
|
||||
Number:ElectricCurrent ALD1_Current "[%.1f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:current"}
|
||||
Number:Power ALD1_Active_Power "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:active_power"}
|
||||
Number:Power ALD1_Reactive_Power "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:reactive_power"}
|
||||
Number:Dimensionless ALD1_Power_Factor "[%.2f]" {channel="modbus:ald1Bidirectional:8b6e85623b:power_factor"}
|
||||
```
|
||||
|
||||
### .sitemap
|
||||
|
||||
```
|
||||
sitemap ald1 label="ALD1 Energy Meter"
|
||||
{
|
||||
Default item=ALD1_Total_Energy label="Total Energy"
|
||||
Default item=ALD1_Feeding_Back_Energy label="Feeding Back Energy"
|
||||
Default item=ALD1_Voltage label="Voltage"
|
||||
Default item=ALD1_Current label="Current"
|
||||
Default item=ALD1_Active_Power label="Active Power"
|
||||
Default item=ALD1_Reactive_Power label="Reactive Power"
|
||||
Default item=ALD1_Power_Factor label="Power Factor"
|
||||
}
|
||||
```
|
||||