[lcn] Add shutter positioning/angle, operating hours counters, tunable white, regulator mode, beeping (#13056)
* [lcn] Add shutter positioning/angle, operating hours counters, tunable white, regulator mode, beeping Also, fix possible race condition during connecting, when the PC coupler is not connected to the LCN data wire. Replace discontinued LCN-PKE by LCN-VISU. Signed-off-by: Fabian Wolter <github@fabian-wolter.de>
This commit is contained in:
@@ -1,19 +1,21 @@
|
||||
# LCN Binding
|
||||
|
||||
[Local Control Network (LCN)](https://www.lcn.eu) is a building automation system for small and very large installations.
|
||||
[Local Control Network (LCN)](https://www.lcn.eu) is a building automation system.
|
||||
It is capable of controlling lights, shutters, access control etc. and can process data from several sensor types.
|
||||
It has been introduced in 1992.
|
||||
It was introduced in 1992.
|
||||
|
||||
A broad range of glass key panels, displays, remote controls, sensors and in- and outputs exist.
|
||||
The system can handle up to 30,000 bus members, called modules.
|
||||
LCN modules are available for DIN rail and in-wall mounting and feature versatile interfaces. The bus modules and most of the accessories are developed, manufactured and assembled in Germany.
|
||||
LCN modules are available for DIN rail and in-wall mounting and feature versatile interfaces.
|
||||
The bus modules and most of the accessories are developed, manufactured and assembled in Germany.
|
||||
|
||||
Bus members are inter-connected via a free wire in the standard NYM cable. Wireless components are available, though.
|
||||
Bus members are inter-connected via a free wire in the standard NYM cable.
|
||||
Wireless components are available, though.
|
||||
|
||||

|
||||
|
||||
This binding uses TCP/IP to access the LCN bus via the software LCN-PCHK (Windows/Linux) or the DIN rail device LCN-PKE.
|
||||
**This means 1 unused LCN-PCHK license or a LCN-PKE is required**
|
||||
This binding uses TCP/IP to access the LCN bus via the software LCN-PCHK (Windows/Linux) or the DIN rail device LCN-VISU.
|
||||
**This means 1 unused LCN-PCHK license or a LCN-VISU is required**
|
||||
|
||||
## Supported Things
|
||||
|
||||
@@ -21,8 +23,7 @@ This binding uses TCP/IP to access the LCN bus via the software LCN-PCHK (Window
|
||||
|
||||
Any LCN module that should be controlled or visualized, need to be added to openHAB as a *Thing*.
|
||||
|
||||
LCN modules with firmware versions 120612 (2008) and 170602 (2013) were tested with this binding.
|
||||
No known features/changes that need special handling were added until now (2020).
|
||||
LCN modules with firmware versions 120612 (2008), 170602 (2013) and 1F080A (2021) were tested with this binding.
|
||||
Modules with older and newer firmware should work, too.
|
||||
The module hardware types (e.g. LCN-SH, LCN-HU, LCN-UPP, ...) are compatible to each other and can therefore be handled all in the same way.
|
||||
|
||||
@@ -39,13 +40,13 @@ See [Discover LCN Modules](#discover-lcn-modules).
|
||||
### Bridge: LCN PCK Gateway
|
||||
|
||||
PCK is the protocol spoken over TCP/IP with a PCK gateway to communicate with the LCN bus.
|
||||
Examples for PCK gateways are the *LCN-PCHK* software running on Windows or Linux and the DIN rail mounting device *LCN-PKE*.
|
||||
Examples for PCK gateways are the *LCN-PCHK* software running on Windows or Linux and the DIN rail mounting device *LCN-VISU*.
|
||||
|
||||
For each LCN bus, interfaced to openHAB, a PCK gateway needs to be added to openHAB as a *Thing*.
|
||||
|
||||
Several PCK gateways can be added to openHAB to control multiple LCN busses in distinct locations.
|
||||
|
||||
The minimum recommended version is LCN-PCHK 2.8 (older versions will also work, but lack some functionality).
|
||||
The minimum recommended version is LCN-PCHK 3.3 (older versions will also work, but lack some functionality).
|
||||
Visit [https://www.lcn.eu](https://www.lcn.eu) for updates.
|
||||
|
||||
Thing Type ID: `pckGateway`
|
||||
@@ -130,14 +131,18 @@ If a special command is needed, the [Hit Key](#hit-key) action (German: "Sende T
|
||||
| LCN Feature (English) | LCN Feature (German) | Channel | IDs | Type | Description |
|
||||
|---------------------------------|----------------------------------|------------------------|------|--------------------------------|-------------------------------------------------------------------------------------------------------------------------------|
|
||||
| Dimmer Output Control Single | Ausgang | output | 1-4 | Dimmer, Switch | Sets the dimming value of an output with a given ramp. |
|
||||
| Dimmer Output Control Color | Ausgang Farbe | output | color | Color, Switch | Sets the outputs 1-4 to control an RGBW lamp. |
|
||||
| Tunable White Mode | Tunable White Modus | output | tunablewhite | String | Sets the module's tunable white mode: `DISABLE`: Tunable white disabled. `OUTPUT1`: Output 1 is used for controlling. Output 2 is adjusted automatically. `BOTH`: Output 1 is used to control the brightness. Output 2 controls the temperature. |
|
||||
| Relay | Relais | relay | 1-8 | Switch | Controls a relay and visualizes its state. |
|
||||
| Visualize Binary Sensor | Binärsensor anzeigen | binarysensor | 1-8 | Contact | Visualizes the state of a binary sensor (special channel mapping for some devices). |
|
||||
| LED Control | LED-Steuerung | led | 1-12 | Text (ON, OFF, BLINK, FLICKER) | Controls an LED and visualizes its current state. |
|
||||
| Visualize Logic Operations | Logik Funktion anzeigen | logic | 1-4 | Text (NOT, OR, AND) | Visualizes the result of the logic operation. |
|
||||
| Visualize Binary Sensor | Binärsensor anzeigen | binarysensor | 1-8 | Contact | Visualizes the state of a binary sensor (special channel mapping for some devices). |
|
||||
| LED Control | LED-Steuerung | led | 1-12 | String | Controls an LED and visualizes its current state: `ON`, `OFF`, `BLINK`, `FLICKER` |
|
||||
| Visualize Logic Operations | Logik Funktion anzeigen | logic | 1-4 | String | Visualizes the result of the logic operation: `NOT`, `OR`, `AND` |
|
||||
| Motor/Shutter on Dimmer Outputs | Motor/Rollladen an Ausgängen | rollershutteroutput | 1-4 | Rollershutter | Control roller shutters on dimmer outputs |
|
||||
| Motor/Shutter on Relays | Motor/Rollladen an Relais | rollershutterrelay | 1-4 | Rollershutter | Control roller shutters on relays |
|
||||
| Motor/Shutter on Relays | Motor/Rollladen an Relais | rollershutterrelay | 1-4 | Rollershutter, Dimmer | Control position of roller shutters on relays (Supports UpDown, StopMove, Percent) |
|
||||
| Shutter Slat Angle on Relays | Rollladenlamellen an Relais | rollershutterrelayslat | 1-4 | Rollershutter, Dimmer | Control slat angle of roller shutters on relays (Supports UpDown, StopMove, Percent) |
|
||||
| Variables | Variable anzeigen | variable | 1-12 | Number | Sets and visualizes the value of a variable. |
|
||||
| Regulator Set Setpoint | Regler Sollwert ändern | rvarsetpoint | 1-2 | Number | Sets and visualizes the setpoint of a regulator. |
|
||||
| Regulator Set Mode | Reglerverhalten ändern | rvarmode | 1-2 | String | Sets the mode of the regulator: `HEATING` or `COOLING` |
|
||||
| Regulator Lock | Regler sperren | rvarlock | 1-2 | Switch | Locks a regulator and visualizes its locking state. |
|
||||
| Set Thresholds in Register 1 | Schwellwert in Register 1 ändern | thresholdregister1 | 1-4 | Number | Sets and visualizes a threshold in the given threshold register. |
|
||||
| Set Thresholds in Register 2 | Schwellwert in Register 2 ändern | thresholdregister2 | 1-4 | Number | Sets and visualizes a threshold in the given threshold register. |
|
||||
@@ -158,8 +163,12 @@ If a special command is needed, the [Hit Key](#hit-key) action (German: "Sende T
|
||||
| Access Control | Zutrittskontrolle | code#remotecontrolcode | | Trigger | Receive serial numbers from remote control |
|
||||
| Remote Control Battery Low | Fernbedienung Batterie schwach | code#remotecontrolbatterylow | | Trigger | Triggered when the sending remote control has a low battery |
|
||||
| Host Command (Send Keys) | Kommando an Host (Sende Tasten) | hostcommand#sendKeys | - | Trigger | Receive *send keys* command from LCN module |
|
||||
| Operating Hours Counter Outputs | Betriebsstundenzähler Ausgänge | operatinghourscounter | output[1-4] | Number:Time | Visualize Operating Hours Counter for outputs |
|
||||
| Operating Hours Counter Outputs (rel. Work) | Betriebsstundenzähler Ausgänge (rel. Arbeit) | operatinghourscounter | outputrelativework[1-4] | Number:Time | Visualize Operating Hours Counter for outputs (relative work) |
|
||||
| Operating Hours Counter Relays | Betriebsstundenzähler Relais | operatinghourscounter | relay[1-8] | Number:Time | Visualize Operating Hours Counter for relays |
|
||||
| Operating Hours Counter Binary Sensor | Betriebsstundenzähler Binärsensoren | operatinghourscounter | binarysensor[1-8] | Number:Time | Visualize Operating Hours Counter for binary sensors |
|
||||
| Status Message | Statusmeldungen | - | - | - | Automatically done by openHAB Binding |
|
||||
| Audio Beep | Audio Piepen | - | - | - | Not implemented |
|
||||
| Audio Beep | Audio Piepen | N/A | N/A | N/A | Action: "beep" (see below) |
|
||||
| Audio LCN-MRS | Audio LCN-MRS | - | - | - | Not implemented |
|
||||
| Count/Compute | Zählen/Rechnen | - | - | - | Not implemented |
|
||||
| DALI | DALI | - | - | - | Not implemented |
|
||||
@@ -180,7 +189,7 @@ If a special command is needed, the [Hit Key](#hit-key) action (German: "Sende T
|
||||
| Lock Relays | Sperre Relais | - | - | - | Not implemented |
|
||||
| Lock Thresholds | Sperre Schwellwerte | - | - | - | Not implemented |
|
||||
| Motor Position | Motor Position | - | - | - | Not implemented |
|
||||
| Relay Timer | Relais-Timer | N/A | N/A | N/A | Action: "startRelayTimer": Starts a relay timer for the given relay number with the given duration in milliseconds. |
|
||||
| Relay Timer | Relais-Timer | N/A | N/A | N/A | Action: "startRelayTimer" (see below) |
|
||||
| Send Keys Delayed | Sende Tasten verzögert | - | - | - | Not implemented |
|
||||
| Set S0 Counters | S0-Zähler setzen | - | - | - | Not implemented |
|
||||
| Status Command | Statuskommandos | - | - | - | Not implemented |
|
||||
@@ -415,10 +424,43 @@ when
|
||||
then
|
||||
val actions = getActions("lcn","lcn:module:b827ebfea4bb:17B4196847")
|
||||
// relayNumber=3, duration=90
|
||||
actions.startRelayTimer(3,90)
|
||||
actions.startRelayTimer(3, 90)
|
||||
end
|
||||
```
|
||||
|
||||
### Beep
|
||||
|
||||
This *Action* realizes the LCN commmand "audio" (German: "Piepen").
|
||||
It lets the beeper connected to the LCN module beep.
|
||||
|
||||
When programming an "audio" *Action*, the following parameters can be set:
|
||||
|
||||
*volume* - Sound volume in percent (if null, the previous volume will be used)<br />
|
||||
*tonality* - The tonality as a String. You need to use quotes. See below.<br />
|
||||
*count* - Number of beeps (max. 50)
|
||||
|
||||
Tonalities:
|
||||
|
||||
- "N"=push button hit (normal)
|
||||
- "S"=special
|
||||
- "1"=push button make
|
||||
- "2"=push button break
|
||||
- "3"=standard
|
||||
- "4"=special
|
||||
- "5"=special short
|
||||
- "6"=error
|
||||
- "7"=long
|
||||
|
||||
```
|
||||
rule "Beep when dummy switch changed"
|
||||
when
|
||||
Item Dummy_Switch changed
|
||||
then
|
||||
val actions = getActions("lcn","lcn:module:b827ebfea4bb:b0b029b920")
|
||||
// volume=100, tonality="6", count=2
|
||||
actions.beep(100, "6", 2)
|
||||
end
|
||||
```
|
||||
|
||||
## Caveat and Limitations
|
||||
|
||||
@@ -469,6 +511,7 @@ Switch M10_Relay1 {channel="lcn:module:b827ebfea4bb:S000M010:relay#1"}
|
||||
|
||||
// Roller Shutter on Relays 1+2
|
||||
Rollershutter M10_RollershutterRelay1 {channel="lcn:module:b827ebfea4bb:S000M010:rollershutterrelay#1"}
|
||||
Dimmer M10_RollershutterRelay1Slats {channel="lcn:module:68b8462b:S000M012:rollershutterrelayslat#1"}
|
||||
|
||||
// LEDs
|
||||
String M10_LED1 {channel="lcn:module:b827ebfea4bb:S000M010:led#1"}
|
||||
@@ -545,6 +588,8 @@ sitemap lcn label="My home automation" {
|
||||
|
||||
// Roller Shutter on Relays
|
||||
Default item=M10_RollershutterRelay1 label="Roller Shutter on Relay 1-2"
|
||||
Dimmer item=M10_RollershutterRelay1 label="Roller Shutter Position on Relay 1-2"
|
||||
Default item=M10_RollershutterRelay1Slats label="Roller Shutter Slat Angle on Relay 1-2"
|
||||
|
||||
// LEDs
|
||||
Switch item=M10_LED1 label="LED 1" mappings=[ON=ON, OFF=OFF] // Don't display "Blink" or "Flicker"
|
||||
|
||||
Reference in New Issue